Rosemount 3051S MultiVariable Transmitter
Purchase options
From$1,468.04
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
MultiVariable DP transmitter with static pressure and Pt100 temperature input: 0.04 percent of reading DP accuracy and mass flow calculated inside the transmitter.
Key features
- MultiVariable transmitter measuring differential pressure, static pressure and process temperature in one device
- Calculates mass and energy flow internally from the three inputs, so the control system receives a finished mass flow rather than raw DP
- Ultra for Flow performance: +/-0.04 percent of READING DP accuracy with 200:1 rangedown and 15-year stability
- Measurement type codes: 1 DP + static + temperature, 2 DP + static, 3 DP + temperature, 4 DP only
- Temperature input is Pt100 RTD -200 to 850 C and the sensor is ordered separately; types 1 and 3 require it, types 2 and 4 require none
- Update rates: DP 22 per second, calculated variables 22 per second, RTD interface 1 per second
Key specifications
- Accuracy
- Ultra for Flow performance: +/-0.04 percent of READING differential pressure accuracy, 200:1 rangedown, 15-year stability and 15-year limited warranty. Reading-based accuracy does not degrade as a proportion of the value when the span is set wider than the operating point
- Output signal
- 4-20 mA with HART, or FOUNDATION Fieldbus, carrying differential pressure, static pressure, temperature and calculated mass or energy flow. Calculated variables update at 22 per second, the DP channel at 22 per second and the RTD interface at 1 per second
- Diagnostics
- The three measurements are taken at one device and compensated together inside it, so the control system receives a finished mass flow rather than raw DP plus two correction inputs. The compensation is what keeps a steam or gas reading honest as pressure and temperature move through the day
- Pressure range
- Differential pressure ranges per the 3051S coplanar offering, with static pressure limits of 4,500 psig (310 bar) or 6,092 psig (420 bar) available as CD options. Static pressure range 5 is a sealed gauge sensor
- Variants
- Measurement type codes: 1 DP + static + temperature, 2 DP + static, 3 DP + temperature, 4 DP only. RTD input is required for types 1 and 3 and must be none for types 2 and 4. Isolating diaphragm in 316L, Alloy C-276, tantalum or gold-plated 316L
- Application
- Steam and gas flow where density compensation is worth having, natural gas and utility flow metering, boiler feedwater and steam headers, and any DP flow point that would otherwise need separate pressure and temperature transmitters
Three measurements in one device, and the compensation maths inside it
The Rosemount 3051S MultiVariable measures differential pressure, static pressure and process temperature in a single transmitter, and calculates mass or energy flow from those three inputs inside the device. It replaces what used to be a DP transmitter, a separate pressure transmitter and a separate temperature transmitter, plus a flow computer to combine them — and the reason that matters is not the part count, it is that the three measurements are taken at one place and compensated together.
The accuracy claim, and the two words inside it
Ultra for Flow is quoted at ±0.04 percent of reading DP accuracy with 200:1 rangedown and 15-year stability. The phrase that carries the weight is "of reading", not "of span". An accuracy quoted against span degrades as a proportion of the measured value whenever the span is set wider than the operating point; an accuracy quoted against reading does not. On a flow measurement, where the differential pressure falls with the square of flow and the low end of the range is where most of the operating time is spent, that difference is the entire argument for the Ultra for Flow option over the standard performance class.
What the three inputs actually buy
A DP transmitter measuring flow without compensation reports a value that is only correct at the density and temperature it was configured for. Steam and gas are where that falls apart: density changes with pressure and temperature, so an uncompensated DP reading drifts through the day with nothing wrong with the transmitter. Adding static pressure and temperature lets the device compute mass flow directly, using the fluid properties for the medium and the primary element. The practical result is a flow number in mass units that stays honest as the line conditions move.
The update rate, read properly
The headline is that mass flow is calculated 22 times per second, and the specification table behind it is more interesting: DP updates at 22 per second, calculated variables at 22 per second, and the RTD interface at 1 update per second. So the differential pressure channel is fast, but a temperature-compensated flow is refreshed at the RTD's rate. For steam and gas flow that is entirely adequate — the thermal time constant of the line is minutes, not milliseconds — but it is the honest reading of the number, and it explains why the temperature sensor's installation and response time matter more than the transmitter's update rate.
Configuration choices that decide the part number
Measurement type is an ordering code, not a software setting: 1 is DP + static + temperature, 2 is DP + static, 3 is DP + temperature, 4 is DP only. The temperature input is an RTD (Pt100, -200 to 850 °C) and the sensor is ordered separately — and the code pairing is strict: measurement types 1 and 3 require the RTD input, types 2 and 4 require it to be none. A specification that names the measurement type and forgets the sensor arrives as a transmitter with nothing to compensate with.
Where it fits
Steam and gas flow where density compensation is worth having, natural gas and utility flow metering, boiler feedwater and steam headers, and any DP flow point where a separate pressure and temperature transmitter would mean extra impulse lines, extra penetrations and three devices to keep calibrated. It is also the device that removes a flow computer from a skid — the calculation happens in the transmitter, so the control system receives a finished mass flow rather than raw DP.
Manufacturer reference: Rosemount 3051S Series Pressure Transmitter Product Data Sheet, MultiVariable ordering information, performance specifications and update rates.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Ultra for Flow performance: +/-0.04 percent of READING differential pressure accuracy, 200:1 rangedown, 15-year stability and 15-year limited warranty. Reading-based accuracy does not degrade as a proportion of the value when the span is set wider than the operating point |
| Output signal | 4-20 mA with HART, or FOUNDATION Fieldbus, carrying differential pressure, static pressure, temperature and calculated mass or energy flow. Calculated variables update at 22 per second, the DP channel at 22 per second and the RTD interface at 1 per second |
| Diagnostics | The three measurements are taken at one device and compensated together inside it, so the control system receives a finished mass flow rather than raw DP plus two correction inputs. The compensation is what keeps a steam or gas reading honest as pressure and temperature move through the day |
| Pressure range | Differential pressure ranges per the 3051S coplanar offering, with static pressure limits of 4,500 psig (310 bar) or 6,092 psig (420 bar) available as CD options. Static pressure range 5 is a sealed gauge sensor |
| Variants | Measurement type codes: 1 DP + static + temperature, 2 DP + static, 3 DP + temperature, 4 DP only. RTD input is required for types 1 and 3 and must be none for types 2 and 4. Isolating diaphragm in 316L, Alloy C-276, tantalum or gold-plated 316L |
| Application | Steam and gas flow where density compensation is worth having, natural gas and utility flow metering, boiler feedwater and steam headers, and any DP flow point that would otherwise need separate pressure and temperature transmitters |
| Mounting | Coplanar or in-line mounting on a DP primary element with impulse piping, plus a separate Pt100 RTD installed in the line and wired to the transmitter - the sensor is ordered separately from the transmitter |
| Operating temperature (°C) | Process temperature through the Pt100 RTD input, -200 to 850 C (-328 to 1562 F); the transmitter electronics are rated for their own ambient limits in the housing |