Rosemount 4051SFA Annubar Flow Meter
Purchase options
From$2,721.46
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Averaging pitot DP flow meter for large lines: 0.8 percent flow rate accuracy at 14:1 flow turndown, low permanent pressure loss, liquid, gas or steam.
Key features
- Averaging pitot (Annubar) differential pressure flow meter on the 4051S platform, ordered by fluid type (liquid, gas or steam) and line size from 2 in (51 mm) upward
- An orifice plate is a full-bore restriction that leaves a large permanent pressure loss for the pump to make up continuously; an averaging pitot presents a much smaller blockage, so for the same differential signal more pressure stays in the line
- On large line sizes the cost gap widens with pipe diameter, because an orifice meter needs a flange pair, plate, gaskets and straight run while an Annubar is a probe through one connection
- Flow turndown is the square root relationship in disguise: 14:1 flow turndown is 196:1 of differential pressure, and 28:1 flow turndown is roughly 784:1, which is why the bottom of a DP flow range is where the measurement is weakest
- Performance classes: Ultra-For-Flow 0.8 percent flow rate accuracy at 14:1 flow turndown (28:1 with the universal range option U), or Classic 1.25 percent at 8:1
- The characteristic failure is a plugged impulse line, which reduces the seen differential and reads as lower flow - a plant running gently rather than an instrument fault. The Process Intelligence option with Plugged Impulse Line diagnostic detects it from the signal dynamics
Key specifications
- Accuracy
- Ultra-For-Flow 0.8 percent flow rate accuracy with 14:1 flow turndown, or 28:1 with the universal pressure range option U. Classic 1.25 percent flow rate at 8:1. Because flow relates to differential pressure by a square root, a 14:1 flow turndown is a 196:1 turndown of differential, and 28:1 in flow is roughly 784:1 - which is why the bottom of a DP flow range is where the measurement is weakest
- Output signal
- Flow output by square root extraction from the differential pressure, configurable as volumetric flow, mass flow rate or totalized flow from the display. 4-20 mA with HART and Bluetooth, on the 4051S electronics platform
- Diagnostics
- Device and Loop Integrity diagnostics as standard. Enhanced SIS proof testing and logging for safety instrumented service. Process Intelligence with Plugged Impulse Line diagnostic monitors the pressure signal dynamics to detect a partially blocked tap - the characteristic failure of a DP flow meter, which reduces the differential seen and reads as lower flow, so a plant running gently rather than an instrument fault
- Pressure range
- Set by the 4051S Coplanar sensor module, its range code and the probe and connection ratings. The Annubar probe is inserted through a single connection into the pipe rather than bolted between flanges
- Application
- Flow measurement in large line sizes where the cost, weight and installation of a full-bore meter are the problem: water and wastewater mains, air and combustion ducts, steam headers, gas transmission and large process lines. Ordered by fluid type - liquid, gas or steam - because the sizing depends on density and, for gas and steam, on compressibility
- Operating temperature (°C)
- Set by the probe material, the connection and the 4051S sensor module selected; a steam application additionally requires the impulse lines and transmitter arranged so the legs stay filled with condensate and the transmitter sees the correct reference condition
An orifice plate taxes the pump forever; an Annubar taxes it less
The Rosemount 4051SFA is an averaging pitot (Annubar) differential pressure flow meter built on the 4051S transmitter. It is ordered by fluid type — liquid, gas or steam — and by line size from 2 in (51 mm) upward, with a flow output from square-root extraction, and in two performance classes: Ultra-For-Flow at 0.8 % flow rate accuracy and 14:1 flow turndown (28:1 with the universal range option), or Classic at 1.25 % and 8:1.
The reason it exists is not accuracy. It is the energy that a flow meter costs you every hour it is installed.
Permanent pressure loss is a bill you pay monthly
Every obstruction in a pipe drops pressure, and a flow meter is an obstruction by design — that is how it measures. But there are two different losses. The temporary loss is the differential the transmitter reads, and it recovers downstream. The permanent loss is what stays lost, and a pump or a compressor has to make it up for as long as the line runs.
An orifice plate is a full-bore restriction with a sharp edge: it creates a large permanent loss, often a substantial fraction of the differential it generates. An averaging pitot presents a much smaller blockage — a slender probe across the pipe with ports facing upstream and downstream — so for the same differential signal it leaves more pressure in the line. On a large water or air line with a continuously running pump, that difference is measured in kilowatts, and it is the reason this technology is chosen on big lines rather than on small ones.
The second reason is physical. A 24 in line with an orifice meter needs a flange pair, a plate, gaskets, a straight run upstream and downstream, and the weight and cost of all of it. An Annubar is a probe inserted through a single connection. On large diameters the cost gap widens with the pipe size, because the pipe is what you would otherwise be buying twice.
The turndown is a flow number, and the DP turndown behind it is its square
This is the part that is easy to misread, and it decides whether a DP flow meter suits an application at all.
Differential pressure flow measurement works on the square-root relationship: flow is proportional to the square root of the differential. So a 14:1 flow turndown corresponds to a 196:1 turndown in differential pressure (14 squared), and a 28:1 flow turndown corresponds to roughly 784:1 of differential.
Two consequences follow directly:
The bottom of the range is where DP flow struggles. At one fourteenth of maximum flow, the differential is a hundred and ninety-sixth of its full value — a very small signal, sitting on top of whatever zero offset, static pressure effect and impulse-line error the installation has. That is why the accuracy figure is quoted as a percentage of flow rate with an explicit turndown attached, rather than as a bare percentage.
The universal range option is worth understanding. The 28:1 figure appears only with the universal pressure range option "U". A wider DP range means the same meter can resolve a smaller differential at the low end, which buys flow turndown. If an application genuinely needs to measure from a trickle to full rate, that option is the difference between meeting it and not.
The failure mode is a plugged impulse line, and it reads low
A DP flow meter's weak point is not the transmitter and not the probe: it is the small passage between them. A plugged or partially plugged impulse line reduces the differential the transmitter sees, which reads as lower flow — and a lower flow reading looks like a plant that is running gently, not like a broken instrument.
That is why the diagnostic options on this meter matter more than they look. The Process Intelligence option with Plugged Impulse Line diagnostic monitors the dynamics of the pressure signal to notice that the line has stopped responding — the signature of a partially blocked tap — and reports it. Without that, the discovery happens when somebody compares the meter against a portable instrument or reconciles a mass balance, which may be never.
The middle option, enhanced SIS proof testing with logging, is for safety instrumented service: it structures and records the proof test rather than leaving it as a procedure and a tick box. And the basic Loop Integrity diagnostic watches the electrical loop for the corrosion and moisture that would otherwise masquerade as a drift.
Fluid type is a sizing input, not a label
The meter is ordered as liquid, gas or steam, and that is not administrative. The flow equation uses the fluid's density at operating conditions, and for gas and steam it also has to account for compressibility. Getting the fluid code wrong means the meter computes flow with the wrong relationship — and a meter that is 20 % wrong is not obviously wrong, it is just wrong in a way that reconciles badly at the end of the month.
It also changes the installation. Steam measurement requires the impulse lines and the transmitter to be arranged so the legs stay filled with condensate and the transmitter sees the right reference condition; a gas application on the same pipe needs a different arrangement. The fluid code selects the whole assembly, not just a constant.
Where it fits
Large line sizes where the cost, weight and installation of a full-bore meter are the problem: water and wastewater mains, air and combustion ducts, steam headers, gas transmission and large process lines. It is the natural choice where the permanent pressure loss would otherwise be paid continuously, and where a straight run is available for the probe.
It is the wrong choice where the application needs a wide flow turndown, a very small line, or a viscous fluid that will not develop a clean differential. For those, the integral orifice version of the same family exists because the trade runs the other way: more permanent loss, better behaviour at low flow on a small line.
Manufacturer reference: Rosemount 4051SFA Annubar Flow Meter Product Data Sheet and Quick Start Guide for the performance classes, line sizes, fluid codes, diagnostic options and installation requirements.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Ultra-For-Flow 0.8 percent flow rate accuracy with 14:1 flow turndown, or 28:1 with the universal pressure range option U. Classic 1.25 percent flow rate at 8:1. Because flow relates to differential pressure by a square root, a 14:1 flow turndown is a 196:1 turndown of differential, and 28:1 in flow is roughly 784:1 - which is why the bottom of a DP flow range is where the measurement is weakest |
| Output signal | Flow output by square root extraction from the differential pressure, configurable as volumetric flow, mass flow rate or totalized flow from the display. 4-20 mA with HART and Bluetooth, on the 4051S electronics platform |
| Diagnostics | Device and Loop Integrity diagnostics as standard. Enhanced SIS proof testing and logging for safety instrumented service. Process Intelligence with Plugged Impulse Line diagnostic monitors the pressure signal dynamics to detect a partially blocked tap - the characteristic failure of a DP flow meter, which reduces the differential seen and reads as lower flow, so a plant running gently rather than an instrument fault |
| Pressure range | Set by the 4051S Coplanar sensor module, its range code and the probe and connection ratings. The Annubar probe is inserted through a single connection into the pipe rather than bolted between flanges |
| Application | Flow measurement in large line sizes where the cost, weight and installation of a full-bore meter are the problem: water and wastewater mains, air and combustion ducts, steam headers, gas transmission and large process lines. Ordered by fluid type - liquid, gas or steam - because the sizing depends on density and, for gas and steam, on compressibility |
| Operating temperature (°C) | Set by the probe material, the connection and the 4051S sensor module selected; a steam application additionally requires the impulse lines and transmitter arranged so the legs stay filled with condensate and the transmitter sees the correct reference condition |
| Measuring range | Line sizes from 2 in (51 mm) upward, with each size a separate code. The permanent pressure loss is the point of the technology: an orifice plate is a full-bore restriction with a large unrecovered loss, while an averaging pitot presents a much smaller blockage, so for the same differential signal more pressure stays in the line and the pump has less to make up every hour |