Rosemount 625IR Fixed Gas Detector
Purchase options
From$126.14
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Optical IR point detector for combustible gas, 0-100 percent LEL, with no bead to poison, factory calibration for life and T90 of 2 s with the environment shield.
Key features
- Optical infrared point detector for combustible gas, 0 to 100 percent LEL of methane or propane, with no catalyst bead to poison
- A catalytic bead measures by burning gas on a heated element that silicones, lead, sulphur and halogens coat or alter, leaving the detector reading low without announcing it. Infrared measures absorption where the gas absorbs and nothing else does, so that failure mode does not exist
- The five year unit warranty and fifteen year IR source warranty are the commercial statement of that difference
- T90 of 2 seconds with the environment shield fitted and under 1 second without it, so the protection that keeps rain and washdown off the optics costs roughly half the response time
- Heated optics keep the windows above the dew point, which is why the humidity rating reaches 99 percent relative humidity without water being the limiting factor
- Factory calibration is maintained for life with no field calibration needed, so routine maintenance is a functional gas check rather than a zero and span, using the gas-free tester at 50 percent LEL methane
Key specifications
- Accuracy
- Plus or minus 2 percent of full scale, specified at room temperature +77 F (+25 C) and limited by the accuracy of the calibration gas itself. Factory calibration is maintained for life, so there is no field zero and span
- Output signal
- Analog 4-20 mA, source by default with a sink option (SK). Two alarm relays plus a fault relay on the standalone version. HART communication for configuration and diagnostics
- Diagnostics
- No catalyst to poison and no bead to degrade: silicones, lead, sulphur and halogenated compounds coat a catalytic element and leave it reading low without any fault signal, while an optical detector measures absorption where the gas absorbs and nothing else does. Routine maintenance is a functional gas check with the gas-free tester at 50 percent LEL methane, not a calibration. Warranty 5 years on the unit and 15 years on the IR source
- Pressure range
- Not applicable - an optical point detector with no process pressure connection, rated for ambient pressure in a hazardous area
- Application
- Combustible gas detection in arduous industrial locations where a catalytic bead would be poisoned by the process: offshore and onshore process facilities, pipelines and gas transport, compressor and turbine enclosures, loading terminals, and duct monitoring
- Operating temperature (°C)
- Operating and storage -40 to +167 F (-40 to +75 C), 0 to 99 percent relative humidity. Heated optics keep the windows above the dew point, so condensation cannot fog the detector at dawn
There is no bead to poison, and a fifteen-year warranty is how that is stated
The Rosemount 625IR is an optical infrared point detector for combustible gas, measuring 0 to 100 %LEL of methane or propane, in a stainless housing with heated optics, factory calibration held for life, SIL2 certification available, and a five-year limited warranty — with fifteen years on the IR source itself.
That last figure is the one worth reading twice, because it describes a different instrument from the one most sites are used to. A catalytic bead detector measures gas by burning it on a hot bead and watching the resistance change. The bead is a consumable that degrades, and worse, it can be poisoned: silicones, leaded compounds, sulphur and halogenated compounds coat or chemically alter the catalyst, and the detector goes on working — just reading low. A detector that reads 60 %LEL when the atmosphere is at 90 % is more dangerous than one that has failed outright, because nothing announces it.
An IR detector measures absorption at a wavelength where the gas absorbs and nothing else does. There is no catalyst to coat. That is why the source carries a fifteen-year warranty while a bead would be replaced long before: the comparison is the physics, written as a commercial commitment.
The shield costs you half the response
One specification line is worth quoting in full, because it is a trade rather than a number:
T90 = 2 seconds with the environment shield; T90 less than 1 second without it.
Both figures are for the same detector. The environment shield is the fitting that keeps rain, washdown and dust off the optical surfaces, and its presence inside the optical path roughly doubles the time to 90 % of reading. On a gas detection system that trips a shutdown, one second against two is the difference the logic solver's voting and delay timers are built around — so the choice is made deliberately, in the open, at design time: shield for the exposed location and accept 2 s, or leave it off in a sheltered one and keep the speed.
The same reasoning explains the heated optics. Condensation on an optical window does not merely blind the detector, it can look like absorption, and a detector that fogs at dawn is one that false-alarms at dawn. Heating the optics keeps them above the dew point, which is also why the humidity rating runs to 99 % relative humidity without water being the limiting factor.
Which LEL scale the detector is set to
The ordering table carries a choice most people skip: the calibration gas standard, NFPA (2017) by default or IEC/ISO as an option. The two standards do not assign the same lower explosive limit to the same gas, so the scale the detector is calibrated against has to be the one the site's alarm philosophy and its permit-to-work numbers use.
Getting this wrong does not produce a broken detector; it produces a detector that is right about the gas and wrong about the percentage. A reading of 20 %LEL means one thing on an NFPA scale and something else on an IEC one, and the alarm setpoint inherits the difference. Specify the code to match the site's documentation, and make it part of the handover rather than a line nobody remembers choosing.
No field calibration, so the routine test is a function test
The detector is factory calibrated and the datasheet states that this calibration is maintained for life — no field calibration is ever needed. Accuracy is quoted at ±2 % full scale at 25 °C, limited by the tolerance of the calibration gas itself.
Which changes what maintenance is for. There is no zero-and-span ritual to perform, so the routine activity becomes a functional check: apply a known gas at a known concentration and confirm the detector responds and alarms. The accessory list includes a gas-free tester at 50 %LEL methane for exactly this, along with a duct gas test kit and duct flange kits for the in-duct variants. If the response is wrong, the question is not "what is the new span factor" but "is the window dirty, is the shield blocked, is the source failing" — a physical question, which is why the mosquito net and sunshade are on the accessory list at all.
Point, or in the duct
The 625IR comes as a standalone point detector (F02), or as a duct mounted version reaching 5.9 in (15 cm) or 13.8 in (35 cm) into the duct, with matching flange kits in DIN, JIS and ANSI patterns plus a clamping stainless version.
The two answer different questions. A point detector belongs where gas would accumulate — and where that is depends on the gas: methane is lighter than air and gathers high, propane is heavier and gathers low, which is why the detector is ordered for one specific gas rather than "combustible". A duct detector measures the gas that is actually moving through a ventilation or process duct, which is the right place for a turbine enclosure, a paint booth or a laboratory extract where the hazard is carried away rather than pooling.
Where it fits
Offshore and onshore process areas, pipelines and gas transport, compressor and turbine enclosures, loading terminals and any location where a catalytic bead would be poisoned by the process itself — sulphur compounds, silicones, halogenated solvents. That is the selection rule: if the process contains a known bead poison, the optical detector is not a premium choice, it is the only one that keeps its calibration.
Manufacturer reference: Rosemount 625IR Fixed Gas Detector Product Data Sheet for the model codes, gas types and ranges, accuracy and response figures, ambient limits, accessories and certifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Plus or minus 2 percent of full scale, specified at room temperature +77 F (+25 C) and limited by the accuracy of the calibration gas itself. Factory calibration is maintained for life, so there is no field zero and span |
| Output signal | Analog 4-20 mA, source by default with a sink option (SK). Two alarm relays plus a fault relay on the standalone version. HART communication for configuration and diagnostics |
| Diagnostics | No catalyst to poison and no bead to degrade: silicones, lead, sulphur and halogenated compounds coat a catalytic element and leave it reading low without any fault signal, while an optical detector measures absorption where the gas absorbs and nothing else does. Routine maintenance is a functional gas check with the gas-free tester at 50 percent LEL methane, not a calibration. Warranty 5 years on the unit and 15 years on the IR source |
| Pressure range | Not applicable - an optical point detector with no process pressure connection, rated for ambient pressure in a hazardous area |
| Application | Combustible gas detection in arduous industrial locations where a catalytic bead would be poisoned by the process: offshore and onshore process facilities, pipelines and gas transport, compressor and turbine enclosures, loading terminals, and duct monitoring |
| Operating temperature (°C) | Operating and storage -40 to +167 F (-40 to +75 C), 0 to 99 percent relative humidity. Heated optics keep the windows above the dew point, so condensation cannot fog the detector at dawn |
| Response time | T90 = 2 seconds with the environment shield fitted, and T90 under 1 second without it. The shield that keeps rain, washdown and dust off the optics roughly doubles the time to 90 percent of reading, so the choice is a real trade on a shutdown trip |
| Sensor | Standalone optical infrared sensor (IR) measuring 0 to 100 percent LEL. Gas types methane (default) or propane; the gas is ordered as a specific option because methane is lighter than air and propane is heavier, which decides mounting height. Duct versions reach 5.9 in (15 cm) or 13.8 in (35 cm) into the duct |