Resumen

Detector optico IR de punto para gas combustible, 0-100 %LEL, sin perla catalitica que envenenar, calibracion de fabrica de por vida y T90 de 2 s con el escudo ambiental.

Especificaciones principales

Exactitud
Plus or minus 2 percent of full scale, specified at room temperature +77 F (+25 C) and limited by the accuracy of the calibration gas itself. Factory calibration is maintained for life, so there is no field zero and span
Señal de salida
Analog 4-20 mA, source by default with a sink option (SK). Two alarm relays plus a fault relay on the standalone version. HART communication for configuration and diagnostics
Diagnósticos
No catalyst to poison and no bead to degrade: silicones, lead, sulphur and halogenated compounds coat a catalytic element and leave it reading low without any fault signal, while an optical detector measures absorption where the gas absorbs and nothing else does. Routine maintenance is a functional gas check with the gas-free tester at 50 percent LEL methane, not a calibration. Warranty 5 years on the unit and 15 years on the IR source
Rango de presión
Not applicable - an optical point detector with no process pressure connection, rated for ambient pressure in a hazardous area
Aplicación
Combustible gas detection in arduous industrial locations where a catalytic bead would be poisoned by the process: offshore and onshore process facilities, pipelines and gas transport, compressor and turbine enclosures, loading terminals, and duct monitoring
Temperatura de operación (°C)
Operating and storage -40 to +167 F (-40 to +75 C), 0 to 99 percent relative humidity. Heated optics keep the windows above the dew point, so condensation cannot fog the detector at dawn