Rosemount 9930 Magnetic Level Indicator
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Magnetic level indicator with a dry flag column and a float selected by SG and pressure: no process fluid at the glass, -162 to 454 C, to 3400 psig.
Key features
- Magnetic level indicator: a chamber, a magnet-equipped float and a column of flip flags, with red showing the liquid level and silver the vapor space
- No process liquid contacts the indicator glass, because the indicator is a dry column of flags moved by a magnetic field through the chamber wall rather than a window into the process - which is why minimal leak points and sight glass replacement are on the benefit list
- The float table is a trade curve: as minimum SG rises from 0.58 to 0.86 the float's pressure limit rises from 94 to 948 psig, because a float that floats in a light liquid needs thin walls and displacement while a float that holds pressure needs thick walls and therefore weight
- Titanium floats reach the lightest service at 0.54 SG. The floor is 0.40 SG below which the factory must be consulted, and float pressure rating reaches 3400 psig at 100 F
- Interface measurement requires a minimum delta SG of 0.11, so two similar hydrocarbon fractions or a diluted aqueous layer cannot be resolved - the float sits where buoyancy favours and the indication becomes an average
- Temperature range -260 to 850 F (-162 to 454 C) with the chamber to ASME B31.3 and NACE construction on request, hydrostatically tested to 1.5 times MAWP. The same float can drive external magnetostrictive transmitters and magnetic switches with no second process penetration, and a dual chamber version gives a guided wave radar a calm stilling column in a turbulent vessel
Key specifications
- Accuracy
- Resolution is set by the flag pitch, and the reading is the float position rather than a computed value. The selection constraint is the float: it must float in the process liquid and survive the process pressure, and those two requirements pull opposite ways
- Output signal
- Local flag column, red for liquid and silver for vapour. The same float drives externally mounted magnetostrictive transmitters and magnetic switches through the chamber wall, so a vessel can have local indication, a 4-20 mA signal and alarm contacts with no second process penetration
- Diagnostics
- The float table is a trade curve and reading it correctly is the whole specification: as minimum SG rises from 0.58 to 0.86 the float's pressure limit rises from 94 to 948 psig, because a float that floats in a light liquid needs thin walls and large displacement while one that holds pressure needs thick walls and therefore weight. A float chosen for 0.86 SG in a liquid that actually sits at 0.7 does not float, and the failure is silent - the flags simply stop where they stopped
- Pressure range
- Float pressure rating up to 3400 psig (234.4 bar) at 100 F, with the float's own limit set by its selection: 94 psig for the 0.58 SG float up to 948 psig for the 0.86 SG float. The chamber is designed to ASME B31.3 and can be hydrostatically tested to 1.5 times the MAWP of its flange or pressure rating before shipment, with certificates available
- Application
- Turbulent tanks, heat exchangers, boilers, separators, acid storage and any vessel where a sight glass is being replaced because it is a leak point, a fouling surface or a hazard. A local level that reads without power is the quiet advantage of a mechanical indication
- Mounting
- Chamber with process connections, vent and drain, mounted beside the vessel. A dual chamber version is built for use with the Rosemount 5300, 3308 and 3300 guided wave radars, so the radar measures inside a calm stilling column instead of the open vessel - which is how a radar gets a stable surface on a turbulent, boiling or agitated tank
Nothing is behind the glass except flags
The Rosemount 9930 is a magnetic level indicator: a chamber connected to the vessel, a magnet-equipped float inside it that rises and falls with the liquid, and a column of small flags beside the chamber that flip as the float passes. Red shows the liquid level, silver the vapour space, and a graduated scale beside the flags gives the reading.
That arrangement is the whole point, and it is a safety argument rather than a convenience one. A sight glass is a pressure boundary you stand next to and look through: the process fluid is on the other side of a tube of glass, at line pressure, at eye level. Glass clouds, etches, and occasionally fails, and when it does the operator is in the wrong place at the wrong time.
In a magnetic indicator no process liquid touches the indicator glass, because the indicator is not a window into the process at all — it is a dry column of flags moved by a magnetic field through the chamber wall. The pressure boundary is the chamber, which is a piece of pipe, not a window. The datasheet's own list of benefits reads that way: minimal leak points compared with sight glasses, and sight glass replacement named as an application.
The float table is a trade curve, and it decides the product
A magnetic float has to do two jobs that fight each other: float in the liquid (which wants low density, so thin walls and large displacement) and survive the pressure (which wants thick walls, and thick walls make it heavy). The datasheet publishes the consequence as a selection table, and the shape of that table is the engineering.
| Float | Minimum SG | Maximum pressure |
|---|---|---|
| 316 SST | 0.58 | 94 psig (6.4 bar) |
| 316 SST | 0.76 | 167 psig (11.5 bar) |
| 316 SST | 0.83 | 486 psig (33.5 bar) |
| 316 SST | 0.86 | 948 psig (65.3 bar) |
| Titanium | 0.54 | 178 psig (12.2 bar) |
Read it as a menu of compromises. A float rated for a light liquid at low pressure is a different float from one rated for the same liquid at high pressure, and you cannot have both ends. Titanium appears for the lightest service, not for strength.
So the specification question is not "what is the pressure rating" but "what is the process SG, and what pressure does it run at" — asked together. A float chosen for 0.86 SG in a liquid that actually sits at 0.7 is a float that does not float, and the indication does not fail loudly: the flags simply stop where they stopped.
The floor is 0.40 SG, below which the factory has to be consulted, and the float pressure rating reaches 3400 psig (234.4 bar) at 100 °F in the chamber's own rating — again a different selection path from the float's own limit.
Two liquids need a gap of 0.11 SG
For an interface measurement — two liquids in the same vessel, with the float sitting at the boundary — the datasheet gives a minimum delta SG of 0.11. If the two liquids differ by less than that, the float cannot distinguish them: it will sit at whichever level the buoyancy happens to favour, and the indication becomes an average of something rather than an interface.
This is the number to check before promising an interface measurement on a separator. Oil over water is comfortable; two similar hydrocarbon fractions or a diluted aqueous layer often are not.
The range is unusually wide, and that is the point
−260 to +850 °F (−162 to +454 °C). That spans cryogenic service and high-temperature service in one product family, which is possible precisely because the measuring element is a mechanical float in a metal chamber and the indication is magnetic — there is no electronics in the hot or cold zone, and no fluid in the indicator.
The chamber is designed to ASME B31.3 process piping, with B31.1 power piping available on request and NACE construction on request for sour service. Every chamber can be hydrostatically tested to 1.5 times the MAWP of its flange or pressure rating before shipment, with certificates, material traceability, dye penetrant, radiography and PMI available as documentation.
One float, several outputs
Because the float's field passes through the chamber wall, the same float can drive more than a local indication. Externally mounted magnetostrictive transmitters and magnetic switches read the same float position, so a vessel gets a local flag column, a 4–20 mA signal and alarm contacts without a second process penetration. That is the practical difference from adding an independent transmitter: one hole, one pressure boundary, several outputs.
There is also a dual chamber version built for use with the Rosemount 5300, 3308 and 3300 guided wave radars — the radar measures inside a stilling chamber rather than in the open vessel. On a turbulent tank, a boiling service or a vessel with an agitator, that is how a radar gets a stable surface to look at: the chamber presents the radar with a calm, guided column of liquid while the tank itself is doing whatever it does.
Where it fits
Turbulent tanks, heat exchangers, boilers, separators and acid storage — the applications the datasheet lists — and any vessel where a sight glass is being replaced because it is a leak point, a fouling surface or a hazard. Also wherever a local level must be readable without power, which is the quiet advantage of a mechanical indication: it works when the instrument air, the 24 V supply and the control system do not.
Manufacturer reference: Rosemount 9930 Magnetic Level Indicator Product Data Sheet 00813-0100-4430 for the float selection tables by SG and pressure, minimum delta SG, temperature range, chamber ratings, ASME and NACE construction, and documentation options.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Resolution is set by the flag pitch, and the reading is the float position rather than a computed value. The selection constraint is the float: it must float in the process liquid and survive the process pressure, and those two requirements pull opposite ways |
| Output signal | Local flag column, red for liquid and silver for vapour. The same float drives externally mounted magnetostrictive transmitters and magnetic switches through the chamber wall, so a vessel can have local indication, a 4-20 mA signal and alarm contacts with no second process penetration |
| Diagnostics | The float table is a trade curve and reading it correctly is the whole specification: as minimum SG rises from 0.58 to 0.86 the float's pressure limit rises from 94 to 948 psig, because a float that floats in a light liquid needs thin walls and large displacement while one that holds pressure needs thick walls and therefore weight. A float chosen for 0.86 SG in a liquid that actually sits at 0.7 does not float, and the failure is silent - the flags simply stop where they stopped |
| Pressure range | Float pressure rating up to 3400 psig (234.4 bar) at 100 F, with the float's own limit set by its selection: 94 psig for the 0.58 SG float up to 948 psig for the 0.86 SG float. The chamber is designed to ASME B31.3 and can be hydrostatically tested to 1.5 times the MAWP of its flange or pressure rating before shipment, with certificates available |
| Application | Turbulent tanks, heat exchangers, boilers, separators, acid storage and any vessel where a sight glass is being replaced because it is a leak point, a fouling surface or a hazard. A local level that reads without power is the quiet advantage of a mechanical indication |
| Mounting | Chamber with process connections, vent and drain, mounted beside the vessel. A dual chamber version is built for use with the Rosemount 5300, 3308 and 3300 guided wave radars, so the radar measures inside a calm stilling column instead of the open vessel - which is how a radar gets a stable surface on a turbulent, boiling or agitated tank |
| Operating temperature (°C) | -260 to +850 F (-162 to +454 C). The range is possible because the measuring element is a mechanical float in a metal chamber and the indication is magnetic - there is no electronics in the hot or cold zone and no fluid in the indicator |
| Measuring range | Minimum SG 0.40 (consult the factory below that), with standard floats from 0.54 in titanium and 0.58 to 0.86 in 316 stainless steel. For interface measurement between two liquids the minimum delta SG is 0.11 - below that the float cannot distinguish them and the indication becomes an average of something rather than an interface |
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer