Overview
In-situ zirconia oxygen analyzer for flue gas: 0-10 percent O2 factory range to 50 percent, 0.02 percent detection limit, diffuser chosen by duct temperature.
Key features
- In-situ zirconia oxygen analyzer for furnace and boiler flue gas: factory range 0 to 10 percent O2, user range to 50 percent, detection limit 0.02 percent O2
- Measuring in the duct removes the extractive sample system entirely, so there is no sample line to plug with ash, no pump to fail, no cooler to flood and no filter to load up while the analyzer keeps reporting a number
- The diffuser decides probe life and is chosen by temperature: stainless steel snubber to 750 F (400 C), ceramic or Alloy C-276 to 1300 F (704 C)
- Flame safety interlock powers down the heater when the burner flame is lost, which matters because a hot zirconia cell in a duct carrying unburnt gas is an ignition source
- Reference air is a consumable the installation has to provide: clean dry instrument air at 20 psi and 2 scfh. If it is wet or contaminated the cell does not stop working, it produces a wrong but plausible reading because the reference has changed
- Measurement drift is published at three concentrations - 0.05 percent O2 per month at 0.4 percent, 0.1 at 8 percent, 0.25 at 20 percent - so the calibration interval follows the operating point. The SPS 4001B autocalibration system sequences the gases automatically
Key specifications
- Accuracy
- Repeatability 0.75 percent of reading or 0.05 percent O2, whichever is greater, from 0 to 10 percent; 1 percent of reading above 10 percent. Lowest detection limit 0.02 percent O2. The stoichiometric advanced feature repeats to 0.2 percent across an O2 deficiency of 0 to 2 percent
- Output signal
- 4-20 mA analog output with configurable lower and upper range values (LRV 0 to 49 percent O2, URV 1 to 50 percent O2), local operator interface rotatable in 90 degree steps, and relay or autocalibration output options. Remote electronics in an explosion-proof housing rated ATEX/IECEx Ex db and Class I Division/Zone 1
- Diagnostics
- Measurement drift is published at three concentrations: 0.05 percent O2 per month at 0.4 percent, 0.1 at 8 percent and 0.25 at 20 percent, so the calibration interval follows the operating point. Reference air must be clean, dry instrument air at 20 psi and 2 scfh - if it is wet or contaminated the cell keeps working and reports a wrong but plausible reading, because the reference itself has changed. The SPS 4001B autocalibration system sequences low and high calibration gases automatically on a timer, relay or manual command
- Pressure range
- Not applicable in the usual sense - the probe is inserted into a duct at essentially atmospheric pressure. The installation limits are the duct temperature and the probe insertion depth rather than a pressure rating
- Application
- Excess oxygen in furnace and boiler flue gas for combustion trim, efficiency monitoring and emissions support: process heaters, kilns and incinerators. The probe sits in the duct, which removes the extractive sample system - and with it the sample line that plugs with ash, the pump that fails and the cooler that floods
- Operating temperature (°C)
- Diffuser limits set the maximum: stainless steel snubber 750 F (400 C), ceramic or Alloy C-276 1300 F (704 C). Selecting a stainless diffuser for a duct above 400 C is not a marginal error, it is a probe that fails early and repeatedly
The probe lives in the duct, so the duct decides its life
The Rosemount CX2100 is an in-situ oxygen analyzer that measures excess oxygen directly in furnace and boiler flue gas with a zirconia cell. Factory range 0 to 10 % O2, user range to 50 %, detection limit 0.02 % O2, repeatability ±0.75 % of reading or 0.05 % O2 below 10 %, and available as an integral probe or as the explosion-proof CX2100TR remote transmitter.
Excess oxygen is the number a combustion engineer actually controls: too little and the burner makes CO and unburnt fuel, too much and every extra percent is heated nitrogen going up the stack. Getting that number continuously, on the right side of the trade, is worth real money in fuel — which is why the analyzer exists, and why its reliability matters more than its last digit of accuracy.
In-situ, because a sampling system is a maintenance department
The alternative to an in-situ probe is an extractive system: a sample probe, a heated line, a pump, a cooler, a filter and an analyzer in a shelter. Every one of those components is a place for wet, dirty flue gas to cause trouble — a line that plugs with ash, a cooler that floods, a pump that fails, a filter that loads up. The analyzer stays accurate while the sample system quietly stops delivering a representative sample.
An in-situ probe puts the measuring cell in the duct. There is no sample line to plug and no pump to fail. What it costs is accessibility: the probe is now in the flue, at flue temperature, and everything about its life is decided by that environment.
The diffuser is the life-limiting part, and it is chosen by temperature
The cell is protected by a diffuser, and the diffuser is what decides how long the probe survives in a given duct:
| Diffuser | Temperature limit |
|---|---|
| Stainless steel snubber | 750 °F (400 °C) |
| Ceramic | 1300 °F (704 °C) |
| Alloy C-276 | 1300 °F (704 °C) |
That table is the specification to argue about, not the accuracy. A probe selected with a stainless diffuser for a duct that runs at 600 °C is not a slightly wrong choice; it is a probe that will fail early and repeatedly, and the replacement interval becomes the maintenance plan. Above roughly 400 °C the answer is ceramic or C-276, and between the two the selection is about the chemistry of the ash and the gas rather than about temperature — C-276 for reducing or sulphur-bearing service, ceramic where the environment is abrasive and the budget allows.
The probe length is the second half of the same decision: it has to reach far enough into the duct to see representative gas, without being so long that it becomes a cantilever in a fast stream. The datasheet gives insertion depths per diffuser type because those two constraints have to be reconciled on the actual duct.
A heater in a flue needs an interlock, and this one has it
A zirconia cell only works hot — the probe carries a heater that keeps it at operating temperature. In a flue carrying unburnt gas, a hot element is an ignition source, which is why the flame safety interlock is on the feature list: if the burner flame is lost, the interlock powers down the heater.
That is a safety function rather than a convenience, and it belongs in the safety review rather than the instrument list. It is also a reason to prefer an analyzer that has it over one that does not, in any application where a flame-out is credible.
Reference air is the consumable nobody budgets for
A zirconia cell measures the ratio between the oxygen in the flue gas and the oxygen on its other side. That other side is reference air: clean, dry instrument air, regulated to 20 psi at 2 scfh.
Two consequences follow, and the second is the dangerous one. The utility has to exist at the probe — a plant that installs the analyzer and not the air line has an analyzer that reads nothing. And if the reference air supply becomes contaminated or wet, the cell does not stop working: it produces a wrong but plausible oxygen reading, because the reference has changed and the cell is faithfully reporting the new ratio. Reference air quality is part of the measurement, which is why it is specified in the same table as the calibration gases.
The calibration gases are specified to bracket the operating point — 0.4 to 2 % O2 low, 8 to 21 % O2 high, at 20 psi and 5 scfh — because calibrating a 3 % application with a 21 % gas tests a part of the curve that never runs. The datasheet says it directly: the gases should reflect the critical operating range.
The drift table is a calibration interval
Drift is published at three concentrations rather than one, and the shape decides the maintenance plan:
| Operating O2 | Maximum drift |
|---|---|
| 0.4 % | ±0.05 % O2 per month |
| 8 % | ±0.1 % O2 per month |
| 20 % | ±0.25 % O2 per month |
A tight-trim application running at 2 to 3 % O2 drifts by a fraction of what a high-excess application does, in absolute terms, which is fortunate because that is also where a fraction of a percent matters. Reading the table against your own operating point gives the interval: at 0.05 % per month, a ±1 % budget is twenty months of drift; at 0.25 % per month it is four.
Then the SPS 4001B autocalibration system removes the labour from that interval — it sequences the calibration gases automatically, on a manual command, a timer, or a contact relay, with the flow meters and the reference air regulator included in the manifold. One SPS 4001B calibrates one analyzer.
Where it fits
Boiler and furnace flue gas, process heaters, kilns and incinerators — combustion trim, efficiency monitoring and emissions support. Choose the diffuser from the duct temperature and chemistry first, size the probe to the duct, plan the reference air and calibration gas lines as part of the installation, put the flame safety interlock into the safety review, and take the remote electronics version where the transmitter needs to sit somewhere a person can reach without standing on the duct.
Manufacturer reference: Rosemount CX2100 In-Situ Oxygen Analyzer Product Data Sheet for ranges and performance, drift by concentration, diffuser temperature limits, calibration gas and reference air requirements, probe lengths and certifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Repeatability 0.75 percent of reading or 0.05 percent O2, whichever is greater, from 0 to 10 percent; 1 percent of reading above 10 percent. Lowest detection limit 0.02 percent O2. The stoichiometric advanced feature repeats to 0.2 percent across an O2 deficiency of 0 to 2 percent |
| Output signal | 4-20 mA analog output with configurable lower and upper range values (LRV 0 to 49 percent O2, URV 1 to 50 percent O2), local operator interface rotatable in 90 degree steps, and relay or autocalibration output options. Remote electronics in an explosion-proof housing rated ATEX/IECEx Ex db and Class I Division/Zone 1 |
| Diagnostics | Measurement drift is published at three concentrations: 0.05 percent O2 per month at 0.4 percent, 0.1 at 8 percent and 0.25 at 20 percent, so the calibration interval follows the operating point. Reference air must be clean, dry instrument air at 20 psi and 2 scfh - if it is wet or contaminated the cell keeps working and reports a wrong but plausible reading, because the reference itself has changed. The SPS 4001B autocalibration system sequences low and high calibration gases automatically on a timer, relay or manual command |
| Pressure range | Not applicable in the usual sense - the probe is inserted into a duct at essentially atmospheric pressure. The installation limits are the duct temperature and the probe insertion depth rather than a pressure rating |
| Application | Excess oxygen in furnace and boiler flue gas for combustion trim, efficiency monitoring and emissions support: process heaters, kilns and incinerators. The probe sits in the duct, which removes the extractive sample system - and with it the sample line that plugs with ash, the pump that fails and the cooler that floods |
| Operating temperature (°C) | Diffuser limits set the maximum: stainless steel snubber 750 F (400 C), ceramic or Alloy C-276 1300 F (704 C). Selecting a stainless diffuser for a duct above 400 C is not a marginal error, it is a probe that fails early and repeatedly |
| Response time | Measured in situ with no sample transport delay to add to it - the cell sees the duct gas directly, which is the practical advantage over an extractive system where the sample has to travel through a heated line, a cooler and a filter before it is measured |
| Measuring range | Factory calibrated 0 to 10 percent O2; user configurable with a lower range limit of 0 to 10 percent and an upper range limit of 0 to 50 percent O2 |