Resumen

Analizador de oxigeno in situ por zirconia para gas de combustion: rango de fabrica 0-10 por ciento O2 hasta 50 por ciento, limite de deteccion 0.02 por ciento y difusor elegido por la temperatura del conducto.

Especificaciones principales

Exactitud
Repeatability 0.75 percent of reading or 0.05 percent O2, whichever is greater, from 0 to 10 percent; 1 percent of reading above 10 percent. Lowest detection limit 0.02 percent O2. The stoichiometric advanced feature repeats to 0.2 percent across an O2 deficiency of 0 to 2 percent
Señal de salida
4-20 mA analog output with configurable lower and upper range values (LRV 0 to 49 percent O2, URV 1 to 50 percent O2), local operator interface rotatable in 90 degree steps, and relay or autocalibration output options. Remote electronics in an explosion-proof housing rated ATEX/IECEx Ex db and Class I Division/Zone 1
Diagnósticos
Measurement drift is published at three concentrations: 0.05 percent O2 per month at 0.4 percent, 0.1 at 8 percent and 0.25 at 20 percent, so the calibration interval follows the operating point. Reference air must be clean, dry instrument air at 20 psi and 2 scfh - if it is wet or contaminated the cell keeps working and reports a wrong but plausible reading, because the reference itself has changed. The SPS 4001B autocalibration system sequences low and high calibration gases automatically on a timer, relay or manual command
Rango de presión
Not applicable in the usual sense - the probe is inserted into a duct at essentially atmospheric pressure. The installation limits are the duct temperature and the probe insertion depth rather than a pressure rating
Aplicación
Excess oxygen in furnace and boiler flue gas for combustion trim, efficiency monitoring and emissions support: process heaters, kilns and incinerators. The probe sits in the duct, which removes the extractive sample system - and with it the sample line that plugs with ash, the pump that fails and the cooler that floods
Temperatura de operación (°C)
Diffuser limits set the maximum: stainless steel snubber 750 F (400 C), ceramic or Alloy C-276 1300 F (704 C). Selecting a stainless diffuser for a duct above 400 C is not a marginal error, it is a probe that fails early and repeatedly