Rosemount 1195 Integral Orifice Flow Meter
Purchase options
From$604.30
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Integral orifice primary element for 1/2 to 1 1/2 in lines: honed body, self-centering plate and pressure taps in one part, supplied without a transmitter.
Key features
- Integral orifice primary element: honed body, self-centering plate and pressure taps in one part
- Reduces leak points by over 50% compared with a conventional plate between flange unions
- Line sizes 1/2, 1 and 1 1/2 in (15, 25 and 40 mm)
- Discharge coefficient uncertainty up to +/-0.75%; system accuracy to +/-0.95% with an Ultra for Flow transmitter
- 316/316L stainless steel body and plate, Hastelloy C-276 available
- Flanged ANSI and DIN connections, or NPT and beveled ends; supplied without transmitter
Key specifications
- Accuracy
- Discharge coefficient uncertainty up to +/-0.75%; system reference accuracy from +/-2.70% of volumetric flow with a Classic transmitter to +/-0.95% with an Ultra for Flow transmitter, depending on beta; without associated straight run piping the discharge coefficient uncertainty can add 1.5% to 5%
- Pressure rating
- Process connections flanged to ANSI Class 150, 300 and 600 raised face or ring joint, DIN PN16, PN40 and PN100, slip-on or weld-neck, or NPT and beveled ends; pressure limit follows the flange class, for example 18.2 bar (264 psi) on ANSI Class 150 slip-on
- Measurement range
- Line sizes 1/2, 1 and 1 1/2 in (15, 25 and 40 mm); beta ratio (plate bore divided by body inside diameter) selectable from below 0.1 to 0.8
- Application
- Integral orifice primary element for differential pressure flow measurement in small lines; supplied without a transmitter so the DP device can be specified separately
- Mounting
- One-piece honed body with integral plate carrier and pressure taps, reducing leak points by more than 50% compared with a plate between flange unions; 3-valve manifold bolting 46 to 52 N m and plate carrier bolts 81 N m
- Dimensions
- Element alone weighs 1.8 kg (4 lb) for 1/2 in, 2.7 kg (6 lb) for 1 in and 3.6 kg (8 lb) for 1 1/2 in; roughly double with standard-length flanged piping
The primary element on its own
The Rosemount 1195 is an integral orifice primary element: a honed pipe section with a self-centering orifice plate and pressure taps, supplied without a transmitter. It is the mechanical half of a small-bore DP flow measurement, and it exists so that the part where the flow is actually conditioned and measured is made properly rather than assembled on site.
What integral means here
In a conventional orifice installation the plate sits between two flange unions on a piece of pipe, and the pressure taps are drilled and welded separately. That means the inside diameter is whatever the pipe came as, the plate centring depends on the fit, and every joint is a potential leak. The 1195 combines the spool, the plate carrier and the taps into one body: the bore is honed to a known dimension, the plate centres itself, and the number of leak points drops by more than half.
Where the accuracy comes from
Discharge coefficient uncertainty is up to ±0.75%. Combined with a Rosemount transmitter the system reference accuracy runs from ±2.70% of volumetric flow at the worst beta with a Classic transmitter, through ±1.20% at beta 0.2 to 0.6, to ±0.95% with an Ultra for Flow transmitter at 10:1 turndown. Two caveats belong beside those numbers: without associated straight run piping the discharge coefficient uncertainty can add 1.5% to 5%, and the beta ratio is the bore divided by the body inside diameter — which is exactly the quantity the honed body fixes.
Sizes and connections
Half-inch, one-inch and inch-and-a-half lines (15, 25 and 40 mm). Process connections are flanged — ANSI Class 150, 300 and 600 raised face or ring joint, DIN PN16, PN40 and PN100, slip-on or weld-neck — or threaded NPT and beveled ends. Pressure limits follow the flange class: for example 18.2 bar (264 psi) on an ANSI Class 150 slip-on at the low end of the temperature range, rising with class. Transmitter connections are 2⅛ in centre-to-centre, with DIN 19213 available.
Materials and weight
Body and plate are 316/316L stainless steel, cast CF8M per ASTM A351 for the body, with Hastelloy C-276 available as an alternative. The element alone weighs 1.8 kg in half-inch, 2.7 kg in one-inch and 3.6 kg in inch-and-a-half; with standard-length flanged piping those figures roughly double. The 3-valve manifold bolting torque is 46 to 52 N·m, and the plate carrier bolts to 81 N·m.
Why specify the bare element
Because the transmitter may already be a plant standard, or may need to be a specific model for the control system. Buying the element alone lets the DP transmitter be chosen separately — a 3051, a 3051S, or a multivariable unit for gas and steam where static pressure and temperature are needed to compute mass flow. It also suits spares and replacements where the transmitter is fine and the spool is not.
Manufacturer reference: Rosemount Integral Orifice Flowmeter Series Product Data Sheet, 00813-0100-4686 Rev MA.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Discharge coefficient uncertainty up to +/-0.75%; system reference accuracy from +/-2.70% of volumetric flow with a Classic transmitter to +/-0.95% with an Ultra for Flow transmitter, depending on beta; without associated straight run piping the discharge coefficient uncertainty can add 1.5% to 5% |
| Pressure rating | Process connections flanged to ANSI Class 150, 300 and 600 raised face or ring joint, DIN PN16, PN40 and PN100, slip-on or weld-neck, or NPT and beveled ends; pressure limit follows the flange class, for example 18.2 bar (264 psi) on ANSI Class 150 slip-on |
| Measurement range | Line sizes 1/2, 1 and 1 1/2 in (15, 25 and 40 mm); beta ratio (plate bore divided by body inside diameter) selectable from below 0.1 to 0.8 |
| Application | Integral orifice primary element for differential pressure flow measurement in small lines; supplied without a transmitter so the DP device can be specified separately |
| Mounting | One-piece honed body with integral plate carrier and pressure taps, reducing leak points by more than 50% compared with a plate between flange unions; 3-valve manifold bolting 46 to 52 N m and plate carrier bolts 81 N m |
| Dimensions | Element alone weighs 1.8 kg (4 lb) for 1/2 in, 2.7 kg (6 lb) for 1 in and 3.6 kg (8 lb) for 1 1/2 in; roughly double with standard-length flanged piping |
| Transmitter compatibility | Mounts directly to Rosemount 3051, 3051S and multivariable transmitters; 2 1/8 in (54 mm) centre-to-centre connections with DIN 19213 available |
| Material of construction | 316/316L stainless steel body (CF8M per ASTM A351) and plate; Hastelloy C-276 available for body and plate |