Skip to content
MetIQGas intelligence

Technology

Hydrogen monitoring

Hydrogen is the smallest molecule in industrial use, and almost every design decision in hydrogen monitoring follows from that one fact.

Hydrogen is buoyant, diffuses quickly and burns with a flame that is nearly invisible in daylight. It also ignites across a very wide range in air — from about 4% to 75% by volume — which is far wider than methane. A monitoring design that treats hydrogen as "methane but lighter" will misplace its sensors and its alarm logic.

The same properties make it hard to contain: hydrogen permeates many materials and leaks readily at joints, so detection is as much about the fittings and the enclosure as about the sensor.

What changes in practice

  • Sensor placement follows buoyancy: hydrogen accumulates at the highest point of a confined space, not at floor level.
  • Optical absorption is available but weaker than for methane — hydrogen has no strong mid-infrared band, so other principles are often used.
  • Catalytic and electrochemical sensors are common, each with its own cross-sensitivity and poisoning behaviour.
  • A flame that is hard to see makes early detection more valuable, not less.

Continue reading