Technology
Gas sensing principles
Almost every industrial gas measurement reduces to one of a handful of physical effects. Knowing which one a sensor uses tells you most of what it can and cannot do.
A gas sensor is a transducer: it converts a concentration into a signal. The four families below cover the overwhelming majority of fixed industrial monitoring, and they differ in what they measure, how selective they are and what they need to stay calibrated.
| Principle | What it measures | Typical strength | Typical limitation |
|---|---|---|---|
| Optical absorption (NDIR, TDLAS) | Absorption of light at a gas-specific wavelength | Selective; no consumable in the optical path | Optics must stay clean and aligned |
| Electrochemical | Current from a gas reacting at an electrode | Low power; good for small concentrations | Cell depletes and needs periodic replacement |
| Catalytic (pellistor) | Heat released by combustion on a catalyst | Simple and well understood for flammable gas | Requires oxygen; poisoned by some compounds |
| Photoionisation (PID) | Ionisation of molecules by UV light | Broad response to many volatile compounds | Not selective between compounds without separation |
Why optical methods dominate open-area methane monitoring
Methane absorbs strongly in the near infrared, and a tunable laser can be locked onto one absorption line. That gives a measurement that is selective against other hydrocarbons, does not consume a cell, and can be made path-averaged — an advantage when the quantity of interest is a plume crossing a site rather than the concentration at one point.
The cost is optical: windows fog, mirrors misalign, and a dirty lens looks like a change in concentration unless the instrument checks itself. Self-checking is therefore part of the measurement design, not an accessory.
Further reading
- IEC 60079-29-1 — gas detectors for flammable gases, performance requirements
- EN 60079-29-2 — selection, installation, use and maintenance of detectors
- HITRAN database — spectroscopic line parameters for optical absorption