Almost every industrial gas measurement reduces to one of a handful of physical effects. Knowing which one a sensor uses tells you most of what it can and cannot do.

A gas sensor is a transducer: it converts a concentration into a signal. The four families below cover the overwhelming majority of fixed industrial monitoring, and they differ in what they measure, how selective they are and what they need to stay calibrated.

Measurement principles at a glance
PrincipleWhat it measuresTypical strengthTypical limitation
Optical absorption (NDIR, TDLAS)Absorption of light at a gas-specific wavelengthSelective; no consumable in the optical pathOptics must stay clean and aligned
ElectrochemicalCurrent from a gas reacting at an electrodeLow power; good for small concentrationsCell depletes and needs periodic replacement
Catalytic (pellistor)Heat released by combustion on a catalystSimple and well understood for flammable gasRequires oxygen; poisoned by some compounds
Photoionisation (PID)Ionisation of molecules by UV lightBroad response to many volatile compoundsNot selective between compounds without separation
Descriptions are generic; the sensor a given MetIQ deployment uses depends on the gas, the environment and the required measurement.

Why optical methods dominate open-area methane monitoring

Methane absorbs strongly in the near infrared, and a tunable laser can be locked onto one absorption line. That gives a measurement that is selective against other hydrocarbons, does not consume a cell, and can be made path-averaged — an advantage when the quantity of interest is a plume crossing a site rather than the concentration at one point.

The cost is optical: windows fog, mirrors misalign, and a dirty lens looks like a change in concentration unless the instrument checks itself. Self-checking is therefore part of the measurement design, not an accessory.

Further reading

  1. IEC 60079-29-1 — gas detectors for flammable gases, performance requirements
  2. EN 60079-29-2 — selection, installation, use and maintenance of detectors
  3. HITRAN database — spectroscopic line parameters for optical absorption